Valve actuators
The muscle behind a quarter-turn valve: it turns the stem with air, electricity or oil, on command, and brings the valve home if the power is lost.
The parts that make an actuator work in a plant, the standards behind it, and how to choose between the types.
1Control and accessories
An actuator on its own only turns. These parts make it work in a plant.
Solenoid valve
An electric valve that sends the air to the actuator, or vents it. It is the usual way a control system opens and closes an air actuator.
Pneumatic actuators
Limit switches
Switches or sensors that tell the control system the valve has reached open or closed. They confirm the valve really moved.
Every actuated valve
Positioner
An instrument that compares the wanted position with the real one and adjusts the air to make them match. It makes an actuator modulate smoothly.
Control duties
Air filter and regulator
A filter takes out dirt and water, and a regulator holds the supply at the pressure the actuator was sized for.
Pneumatic actuators
Handwheel
A manual override so the valve can be moved when power is off. It is usually fitted to electric actuators.
Electric actuators
Torque and limit switching
In an electric actuator, a torque switch stops the motor if the valve jams, and limit switches stop it at the ends of travel.
Electric actuators
2Standards
Standards that shape actuator design, mounting and testing.
| Standard | What it covers | Used for |
|---|---|---|
| ISO 5211 | Part-turn actuator attachment | The flange and stem drive that let any actuator fit any valve |
| ISO 12490 | Mechanical integrity and sizing of actuators | Torque margins and strength of the stem connection |
| IEC 60034 | Rotating electrical machines | The motor of an electric actuator |
| EN 15714 | Industrial valves, actuators | Requirements for electric, pneumatic and hydraulic actuators |
| EN 12266-1 | Testing of valves | Shell and seat tests of the valve it drives |
Mounting dimensions follow ISO 5211, so an actuator and a valve from different makers can be matched.
3Which one to choose
Compare the four on what matters to the job.
| Need | Double-acting | Spring-return | Electric | Hydraulic |
|---|---|---|---|---|
| Speed | Very fast | Fast | Slow | Moderate |
| Fail-safe | No (or locked) | Yes, by spring | Battery or none | Accumulator |
| Needs | Air | Air | Power | Oil unit |
| Torque | Medium to high | Medium | Medium to high | Very high |
| Cost | Lowest | Low | Higher | Highest |
A plant with air
Choose
- ✓Spring-return for fail-safe shut-off
- ✓Double-acting for the lowest cost and highest speed
- ✓A positioner for control duty
Avoid
- ✗Using a double-acting actuator where a fail-safe is needed
- ✗An air supply that is wet or dirty
- ✗Sizing at the maximum air pressure
A remote site
Choose
- ✓An electric actuator with a handwheel
- ✓A battery or a spring if fail-safe is needed
- ✓Weatherproof, heated enclosure in the cold
Avoid
- ✗An electric actuator where the valve must close in a second
- ✗A motor that is starting too often
- ✗No manual override
A very large valve
Choose
- ✓Hydraulic with a scotch yoke
- ✓An accumulator for fail-safe
- ✓A gearbox on an electric actuator as an alternative
Avoid
- ✗A rack-and-pinion actuator far above its size range
- ✗An oil unit with no standby pump
- ✗No stroke-time limit on a long pipeline
Common mistakes
- !Sizing on the valve's rated torque without a safety factor, or at the maximum air pressure instead of the minimum.
- !Using the spring torque and the air torque as if they were the same: the actuator must be checked on both.
- !Forgetting that the spring-return actuator is bigger than a double-acting one for the same torque.
- !Making the actuator so fast that it causes a water hammer in the pipeline.
- !Choosing a type that cannot do the fail-safe action the process needs.
💡 Rule of thumb: first decide what the valve does when the supply fails, then pick the energy the site has, and size the torque last, on the worst case.