The question it answers

Classification by action and fail position

What does the valve do if the signal or air is lost?

Every control valve has a safe position, decided by the process rather than the valve. It might be closed, to stop fuel reaching a burner, or open, to keep cooling water flowing. A spring in the actuator drives the valve there if the supply fails.

1The options in detail

1

Air to open (fail closed)

Air pressure pushes the valve open. With no air, the spring closes it.

OpenSupply side: 6.0 bar
Far side: 6.0 bar
Drag to rotate · hover a dot for its name

How it works

The air acts on one side of the diaphragm and the spring on the other. More signal pressure compresses the spring and lifts the plug. If the air is lost, the spring pushes the plug back onto the seat.

Strengths

  • ✓Valve closes on failure.
  • ✓The usual choice where closed is safe.
  • ✓Easy to understand and test.

Limits

  • !Not suitable where flow must continue.
  • !Needs a supply of air to stay open.

Where it is used

  • •Fuel and chemical feeds.
  • •Steam to a process.
2

Air to close (fail open)

Air pressure pushes the valve closed. With no air, the spring opens it.

OpenSupply side: 6.0 bar
Far side: 6.0 bar
Drag to rotate · hover a dot for its name

How it works

The spring sits under the diaphragm and holds the plug open. Air pressure on top pushes the diaphragm and plug down onto the seat. When the air is lost the spring opens the valve.

Strengths

  • ✓Valve opens on failure.
  • ✓Right where flow must never stop.
  • ✓Used for cooling and relief.

Limits

  • !Not suitable where closed is safe.
  • !Needs air to stay closed.

Where it is used

  • •Cooling water.
  • •Vents and bypasses.
3

Fail in place

On loss of signal the valve stays where it was.

OpenSupply side: 6.0 bar
Far side: 6.0 bar
Drag to rotate · hover a dot for its name

How it works

A locking device or a piston actuator traps the air or oil, holding the stem still. Some systems use a second valve to lock the pressure in.

Strengths

  • ✓No sudden change in the process.
  • ✓Good where either extreme is unsafe.
  • ✓Avoids upsets from a brief signal glitch.

Limits

  • !The valve may stay in a bad position.
  • !Needs a plan for when it must move.

Where it is used

  • •Large processes that must not be disturbed.
  • •Systems with a separate safety shut-down.

How to choose

  • →Closed is the safe state: air to open.
  • →Open is the safe state: air to close.
  • →Neither extreme is safe: fail in place, with a safety system.

Common mistakes

  • !Choosing the fail position for convenience instead of safety.
  • !Forgetting the failure of the signal and the failure of the air are different.
  • !Never testing the spring.