← Back

Gate valves

A straight-through door for the flow: fully open or fully shut.

Your dutyClean waterDN 20010 bar20 °C400 m³/hEdit duty

Step 6 of 7

6Calculations

These use your duty, the construction and the materials from the earlier steps, so nothing is typed again. Each result shows its formula, and a pass or CHECK mark. Change a value here only if you know better than the default.

1. Pressure drop and velocity

Kv = 0.04·DN² / √ζ   ·   ΔP = ζ·ρ·v² / 2   ·   v = Q / A

Density
1,000 kg/m³
Velocity
3.54 m/s
ζ
0.15
Kv
4,131 m³/h
ΔP
0.009 bar
CHECKVelocity at or below 3 m/s for this serviceOKFully open (not throttling)
  • !The line velocity is above the usual limit for this service. Check the pipe size, or accept more noise, erosion and pressure loss.

The loss coefficient is a typical textbook value. Fully open it is reliable, but published figures for a part-open gate differ between sources by up to two or three times. For anything that depends on the part-open loss, use the manufacturer's Cv curve.

2. Stem load and how to operate it

F = ΔP·π/4·D²   ·   thrust = (μ·F + W)·SF   ·   T = thrust·lead / (2π·η)

Friction between wedge and seat
0.20
Force of the pressure on the gate
31.4 kN
Thrust needed
9.9 kN
Stem torque
42 N·m
Stem turns, open to closed
28
Rim pull on the handwheel
227 N

How to operate it

Handwheel

One person can operate it: the rim pull is within about 360 N.

3. Closing time and water hammer

tcrit = 2L / a   ·   ΔP = ρ·a·Δv (t ≤ tcrit)   ·   ΔP ≈ 2·ρ·L·Δv / t (Michaud)

Wave speed
1000 m/s
Closing time
41 s
Critical time 2L/a
1.0 s
Estimated surge
0.9 bar
Allowed surge (assumed: 10 % of design pressure, a rule of thumb)
1.0 bar
Shortest safe closing time
35 s
OKSlow enough: the surge stays within the allowance

Typical – not brand data. This is a pre-selection. Confirm the final choice with the manufacturer and the project specification.