Pressure reducing valves
A self-acting valve that cuts a high supply pressure to a lower, steady one, whatever the supply or the demand does.
1What a pressure reducing valve is
A pressure reducing valve (PRV) takes a high supply pressure and delivers a lower, steady pressure downstream. It runs on the pipe pressure alone: no power, no controller.
Imagine it
Think of the tap on a mains-fed shower with a pressure regulator behind the wall. The street pressure rises and falls all day, but the pressure at the shower stays the same. The regulator feels the pressure on its downstream side, and closes a little when it is too high and opens a little when it is too low.
- Job
- Cut a high supply pressure to a lower, steady one
- How it senses
- The downstream pressure pushes on a diaphragm or piston against a spring
- Energy
- None needed: the pipe pressure moves it
- Best at
- Steam, compressed air and water systems that need a steady, lower pressure
2Watch it work
Slide the demand downstream. A high demand pulls the pressure after the valve down, the diaphragm drops and the plug opens. A low demand lets it rise, and the plug closes. The gauge shows the pressure being held.
Outlet pressure: 6.00 bar (set 4.0)Drag to rotate · hover a dot for its name
- 1The supply comes in at the high pressure, on the left, and goes up through the seat.
- 2Under the diaphragm is the pressure after the valve. It pushes the diaphragm up. The spring above pushes it down. The two forces balance when the outlet pressure is at the set value.
- 3When the demand rises, the outlet pressure dips, the spring wins, and the diaphragm moves down and opens the plug. When the demand falls, the pressure rises, the diaphragm moves up, and the plug closes.
- 4Turning the adjusting screw changes how hard the spring pushes, and so sets the pressure the valve holds.
3How it was invented
Six steps, in order but not dated, took it from a person at a valve to a complete reducing station.
1 / 6
The hand valve
Step 1
A person at the valve
The first way to hold a lower pressure was a valve and a person with a gauge. When the gauge read high, they closed the valve a little. When it read low, they opened it. It worked, but only as long as someone watched, and the person was always a little late.
The problem
The pressure drifts while nobody is watching, and the hand always reacts late.
The answer
Let the pressure itself move the valve.
4The idea behind it
A pressure reducing valve is built on a few simple ideas.
Feedback with no wires
The pressure that is being controlled is the same pressure that moves the valve. Nothing else is needed.
A balance of forces
The pressure on the diaphragm pushes up, the spring pushes down. The plug stops where the two are equal.
The spring sets the pressure
A stronger spring holds a higher outlet pressure. The adjusting screw changes how strong it is.
Throttling, not stopping
A PRV does not stop the flow. It lets through just enough to hold the pressure, and it turns the rest of the pressure into turbulence and noise.
What you gain
- ✓A steady, lower pressure for the equipment and the pipes downstream.
- ✓No power, no signal, and very few parts.
- ✓Protection of lighter pipework, instruments and appliances.
- ✓Less leakage and less wear downstream, because the pressure is lower.
What you pay
- !A direct-acting valve droops: the pressure falls a little as the flow rises.
- !It is a throttling valve, so the pressure drop makes noise and can cause cavitation or wear.
- !It needs a relief valve after it, because a failure can put the full supply pressure on the low-pressure side.
- !Pilots are small and clog, so a fine strainer is needed in front.
5How it compares
Ways to hold a lower pressure, side by side.
| Valve | Holds the pressure by | Accuracy | Needs power | Best at |
|---|---|---|---|---|
| Pressure reducing valve | Its own downstream pressure | Good to very good | No | Steam, air and water |
| Control valve and controller | A transmitter and a controller | Very good | Yes | Wide flow ranges, process lines |
| Fixed orifice | A hole of fixed size | Poor, it varies with the flow | No | Steady flow only |
| Gas pressure regulator | Its own downstream pressure | Good | No | Fuel gas and clean gases |
| Hand valve | A person | Poor | No | Occasional use |
Typical, general guidance. A manufacturer's datasheet decides.