1Pump affinity laws

How pump flow, head and power change with speed.

2The law in plain words, and a picture to remember

In plain words

The pump affinity laws say how a centrifugal pump behaves when its speed changes: flow changes in proportion to the speed, head with its square and power with its cube. The same laws apply to changes of impeller diameter. They hold exactly between similar operating points of the same pump.

Imagine it

Think of a fan. Run it at half speed and you get about half the airflow. But the push you feel falls to a quarter, and the electricity it draws falls to an eighth. A little speed is worth a lot of energy, so a small slowdown saves a great deal.

Memory hook

Flow ∝ N, head ∝ N², power ∝ N³. A 20% slowdown saves about 49% of the power.

3What it depends on, and how

Three things decide how the laws apply.

1

Speed

It scales the whole pump curve.

At 80% speed: 80% flow, 64% head and 51% power.

Q ∝ N, H ∝ N², P ∝ N³

2

Impeller diameter

Trimming the impeller scales the curve in the same way.

A 10% smaller impeller gives about 10% less flow and 19% less head.

Q ∝ D, H ∝ D²

3

The system

The pump runs where its curve meets the system curve, so a system with static head moves the point differently.

The laws are exact for friction-only systems.

similar points

Try it: change the pump speed and watch flow, head and power

A pump's speed is cut by 20%. By roughly how much does the power it uses drop?

0204060050100150200Flow (m³/h)Head (m)

Flow

80 %

Head

64 %

Power

51 %

Power × 0.51 compared with full speed

Flow
109 m³/h
Power with speed control
7.2 kW
Power to get the same flow by throttling
13.9 kW
Saved by slowing the pump instead of throttling
48 %

A slower pump: the power falls by about 49%, far more than the speed.

5Formula and units

Speed N in rpm (or percent), flow in m³/h, head in m, power in kW. The laws use ratios, so any consistent unit works.

Formulas

  • Q₂ / Q₁ = N₂ / N₁
  • H₂ / H₁ = (N₂ / N₁)²
  • P₂ / P₁ = (N₂ / N₁)³
  • Q ∝ D, H ∝ D², P ∝ D³ (impeller trim)

6Why it matters, and common mistakes

Why it matters

  • ✓They predict the effect of a variable-speed drive before you buy it.
  • ✓They explain why throttling wastes power and slowing the pump saves it.
  • ✓They let you scale a pump curve to a new speed or impeller.

Common mistakes

  • !Expecting the power saving to be proportional to the speed cut.
  • !Applying them far from the best-efficiency point or to a system with a large static head.
  • !Ignoring that motor and drive efficiency change at low speed.