1Pump and system curves

Where a pump and a pipe system balance: the operating point.

2Easy definition, and a picture to remember

In plain words

A pump curve shows the head a pump can give at each flow: high head at low flow, falling as the flow rises. A system curve shows the head the pipework needs at each flow: the static lift, plus friction that grows with the flow squared. The pump runs where the two curves cross: the operating point.

Imagine it

Cycle up a hill into a headwind. On a steep, long hill you have little energy left for speed. The pump is the rider, the system is the hill and the headwind. Pedal as hard as you like: you settle at the speed where the effort you give equals the effort the road asks for.

Memory hook

Operating point = pump curve meets system curve. Close a valve and the system curve steepens: less flow, more head. Slow the pump and its curve shrinks.

3What decides it, and how

Three things move the operating point.

1

Pump speed

The whole pump curve scales with the speed: head with its square, flow with the speed itself.

At 80% speed the head at zero flow falls to 64%.

H ∝ N², Q ∝ N

2

System resistance

A throttled valve, a longer pipe or a dirty filter steepens the system curve.

Closing a valve moves the point up the pump curve: lower flow, higher head.

H_sys = H_static + k · Q²

3

Static head

The height or pressure the pump must overcome before anything flows.

A higher tank lifts the whole system curve and cuts the flow.

H_static = Δz + ΔP / ρg

Try it: close a valve, slow the pump and watch the operating point

A valve on the pump's discharge is closed part-way. What happens to the pump's flow and head?

0204060050100150200Flow (m³/h)Head (m)Best efficiency zonePumpSystemstatic head

Flow

114 m³/h

Head

33.8 m

Pump efficiency

75 %

Shaft power

14.0 kW

Close to the best efficiency point: the pump runs efficiently and quietly.

5Units and formulas

Flow in m³/h, head in m of liquid (1 bar of water is about 10.2 m), power in kW. Head does not depend on the liquid's density, but pressure and power do.

Formulas

  • H_pump = H₀ · (1 − (Q / Q_max)²)
  • H_system = H_static + k · Q²
  • P = ρ · g · Q · H / η
  • H ∝ N², Q ∝ N, P ∝ N³

6Why it matters, and common mistakes

Why it matters

  • ✓It shows whether a pump will deliver the flow you need.
  • ✓A pump far from its best-efficiency point wastes energy and wears out faster.
  • ✓It explains why throttling with a valve wastes power, and why a variable-speed drive saves it.

Common mistakes

  • !Choosing a pump from the flow alone, without checking the head.
  • !Adding a safety margin to both flow and head until the pump runs far left of its best point.
  • !Forgetting that a valve wearing or fouling shifts the system curve over time.