1Flow characteristics

How flow changes as a valve opens: linear, equal percentage and quick opening.

2Easy definition, and a picture to remember

In plain words

A valve's flow characteristic is the curve that links how far it is open to how much it flows. Linear: flow rises in step with the opening. Equal percentage: each step raises the flow by the same percentage of what already flows. Quick opening: most of the flow arrives in the first part of the travel.

Imagine it

Think of a car's accelerator. In a linear car every centimetre of pedal adds the same speed. An equal-percentage car is gentle at first and stronger as you press: fine control when little flow is needed. A quick-opening car jumps almost to full power in the first centimetres: good for on-off work, bad for steady control.

Memory hook

Linear: same step, same flow. Equal percentage: same step, same percentage. Quick opening: big flow early. Installed in a real system, every curve bends toward quick opening.

3What decides it, and how

Three things decide how a valve really behaves.

1

Trim shape

The shape of the plug or port sets the inherent curve, measured with a constant pressure drop.

An equal-percentage valve with rangeability 50 passes only 14% at 50% opening.

Kv = Kvs · f(opening)

2

Authority

A valve that takes only a small share of the system pressure drop loses control as it opens, because the pipe takes over.

At authority 0.2 a linear valve already passes about 79% of the flow at 50% opening.

Q/Qmax = 1 / √(1 − β + β/f²)

3

Rangeability

The ratio between the largest and the smallest flow the valve controls well.

A rangeability of 50 means it controls from 2% to 100% of its maximum flow.

R = Q_max / Q_min

Try it: pick a characteristic, set the authority and sweep the valve

A linear valve is installed where it takes only 20% of the system's pressure drop (authority 0.2). Once installed, how does it behave?

00252550507575100100Valve opening (%)Flow (% of maximum)13%

Valve position

40 %

Flow

13 %

Gain: flow change per 1% of opening

0.52 % / %

At this opening the valve passes 13% installed, instead of 10% on its own curve

The pipe takes part of the pressure drop, so the installed curve bends toward quick opening.

5Units and formulas

Opening and flow are shown in percent. Authority β has no unit: 1 means the valve takes the whole pressure drop, 0.5 means half. Rangeability is a ratio.

Formulas

  • linear: f = x
  • equal percentage: f = R^(x − 1)
  • quick opening: f = √x
  • Q/Qmax = 1 / √(1 − β + β / f²)

6Why it matters, and common mistakes

Why it matters

  • ✓The right characteristic keeps a control loop stable across its whole range.
  • ✓A wrong match makes the valve touchy at one end and dead at the other.
  • ✓It is a standard line on every control valve datasheet.

Common mistakes

  • !Judging a valve only by its catalogue curve and ignoring the system.
  • !Choosing a linear valve where the pressure drop changes a lot with flow.
  • !Sizing so large that the valve works only in the first 20% of its travel.