1Signals and fail-safe positions

4–20 mA, pneumatic signals, and what a valve does when power fails.

2Easy definition, and a picture to remember

In plain words

A controller tells a valve where to go with a standard signal: 4 to 20 milliamps, or 3 to 15 psi of air. The signal starts at 4 mA, not 0, so a dead wire (0 mA) cannot be mistaken for a real 0%. When the signal or the air is lost, a spring drives the valve to a set safe position: fail closed or fail open. You choose which, by asking what is safest for the process.

Imagine it

Think of a dead man's switch on a train. If the driver lets go, the train must stop, not carry on. A valve has the same idea built in: a spring that pushes it to the safe position the moment the air or the signal goes. For a fuel line, safe means shut. For a cooling-water line, safe means open.

Memory hook

4 mA = 0%, 20 mA = 100%. If power fails, the spring decides: fail closed for fuel, fail open for cooling.

3What decides it, and how

Three choices set how a valve behaves in normal and failed states.

1

Signal range

4–20 mA (or 3–15 psi) with a 'live zero', so a lost signal is visible.

A reading under 3.6 mA is a fault, not a request for 0% (the NE43 convention; check the device's own fault setting).

mA = 4 + 0.16 · %

2

Action (air to open or close)

Air-to-open valves are fail closed. Air-to-close valves are fail open.

A spring-return actuator moves the valve to the fail position when the air goes.

position = signal, or 100 − signal

3

Fail position

The safe state depends on the process, not on the valve.

Fuel and steam to a reactor: fail closed. Cooling water and relief paths: fail open.

choose by hazard

Try it: set the signal, choose the fail action and then lose the air

The wire carrying the 4–20 mA signal to a fail-closed valve breaks. What does the valve do?

Controller13.6 mAPositioner10.2 psispring abovevalve 60% open
Signal
13.6 mA
Air to the actuator
10.2 psi · 0.68 bar
Valve position
60 % open
Signal health
OK

Normal: the valve follows the signal. Try losing the air or breaking the wire.

5Units and formulas

Electrical: 4–20 mA = 0–100%. Pneumatic: 3–15 psi, or 0.2–1.0 bar. Valve position is in percent open. Fail action is a design choice marked FC, FO or FL (fail in last position).

Formulas

  • mA = 4 + 0.16 · %
  • psi = 3 + 0.12 · %
  • bar = 0.2 + 0.008 · %
  • fail closed: position = signal · fail open: position = 100 − signal

6Why it matters, and common mistakes

Why it matters

  • ✓The fail position is a safety decision: it decides what happens in a power or air failure.
  • ✓A live zero turns a broken wire into a visible alarm instead of a silent error.
  • ✓Knowing the signal ranges lets you check a loop with a meter.

Common mistakes

  • !Choosing fail closed for a line that must stay open to cool or vent.
  • !Assuming 0 mA means 0%: it means the loop is broken.
  • !Forgetting that a spring-return valve also moves when the air supply is cut off by mistake.