1Signals and fail-safe positions
4–20 mA, pneumatic signals, and what a valve does when power fails.
2Easy definition, and a picture to remember
A controller tells a valve where to go with a standard signal: 4 to 20 milliamps, or 3 to 15 psi of air. The signal starts at 4 mA, not 0, so a dead wire (0 mA) cannot be mistaken for a real 0%. When the signal or the air is lost, a spring drives the valve to a set safe position: fail closed or fail open. You choose which, by asking what is safest for the process.
Imagine it
Think of a dead man's switch on a train. If the driver lets go, the train must stop, not carry on. A valve has the same idea built in: a spring that pushes it to the safe position the moment the air or the signal goes. For a fuel line, safe means shut. For a cooling-water line, safe means open.
Memory hook
4 mA = 0%, 20 mA = 100%. If power fails, the spring decides: fail closed for fuel, fail open for cooling.
3What decides it, and how
Three choices set how a valve behaves in normal and failed states.
Signal range
4–20 mA (or 3–15 psi) with a 'live zero', so a lost signal is visible.
A reading under 3.6 mA is a fault, not a request for 0% (the NE43 convention; check the device's own fault setting).
mA = 4 + 0.16 · %
Action (air to open or close)
Air-to-open valves are fail closed. Air-to-close valves are fail open.
A spring-return actuator moves the valve to the fail position when the air goes.
position = signal, or 100 − signal
Fail position
The safe state depends on the process, not on the valve.
Fuel and steam to a reactor: fail closed. Cooling water and relief paths: fail open.
choose by hazard
Try it: set the signal, choose the fail action and then lose the air
The wire carrying the 4–20 mA signal to a fail-closed valve breaks. What does the valve do?
- Signal
- 13.6 mA
- Air to the actuator
- 10.2 psi · 0.68 bar
- Valve position
- 60 % open
- Signal health
- OK
Normal: the valve follows the signal. Try losing the air or breaking the wire.
5Units and formulas
Electrical: 4–20 mA = 0–100%. Pneumatic: 3–15 psi, or 0.2–1.0 bar. Valve position is in percent open. Fail action is a design choice marked FC, FO or FL (fail in last position).
Formulas
- mA = 4 + 0.16 · %
- psi = 3 + 0.12 · %
- bar = 0.2 + 0.008 · %
- fail closed: position = signal · fail open: position = 100 − signal
6Why it matters, and common mistakes
Why it matters
- ✓The fail position is a safety decision: it decides what happens in a power or air failure.
- ✓A live zero turns a broken wire into a visible alarm instead of a silent error.
- ✓Knowing the signal ranges lets you check a loop with a meter.
Common mistakes
- !Choosing fail closed for a line that must stay open to cool or vent.
- !Assuming 0 mA means 0%: it means the loop is broken.
- !Forgetting that a spring-return valve also moves when the air supply is cut off by mistake.
Keep going: more on valves and systems
Flow characteristics
How flow changes as a valve opens: linear, equal percentage and quick opening.
Open lesson →
Valve authority and rangeability
How much of the system pressure drop the valve controls, and how far it can turn down.
Open lesson →
Flashing and choked flow
When the flow stops rising however much the pressure drop grows.
Open lesson →
Minor losses (K factor)
What valves, bends and reducers cost in pressure.
Open lesson →
Pump and system curves
Where a pump and a pipe system balance: the operating point.
Open lesson →
NPSH
Whether a pump has enough pressure at its inlet to avoid cavitation.
Open lesson →
Gas and steam flow
Compressible flow through a valve: expansion and the sonic limit.
Open lesson →
Control loop basics
Setpoint, gain, deadband and PID in plain words.
Open lesson →
Leakage classes and shut-off
What tight shut-off really means: how much a closed valve may leak.
Open lesson →
Noise and vibration
Why valves are loud, how sound adds up and fades, and what to do about it.
Open lesson →
Materials and corrosion
Choosing a valve body material that survives the fluid and the temperature.
Open lesson →