1Leakage classes and shut-off
What tight shut-off really means: how much a closed valve may leak.
2Easy definition, and a picture to remember
Seat leakage is the fluid that gets past a valve that is fully closed. Standards (ANSI/FCI 70-2 and IEC 60534-4) group the allowed amount into classes from I to VI. Class IV is the usual standard for control valves. Class V and VI are for tight shut-off, and a valve not built for them cannot meet them.
Imagine it
Think of a closed tap that still drips. A drip a minute is fine on a garden tap and a disaster if the fluid is fuel gas or acid. Leakage classes put a number on how much drip is acceptable, so everyone means the same thing when they say tight.
Memory hook
Control valves are Class IV by default: 0.01% of rated flow. If the process needs real shut-off, ask for Class V or VI, or add a separate on-off valve.
3What decides it, and how
Three things decide how much a closed valve leaks.
The class
Classes II to IV allow a share of the valve's rated flow. Classes V and VI use tiny fixed rates.
For a Kv 100 valve of DN 100 at 3.4 bar, Class V allows about three thousand times less than Class IV.
II 0.5% · III 0.1% · IV 0.01%
Seat design
Metal seats leak more. Soft seats (PTFE, elastomer) seal better but have temperature and pressure limits.
Soft seats can reach Class VI. Metal seats usually reach Class IV or V.
seat material
Size and pressure
Bigger valves and higher pressure drops allow more leakage in absolute terms.
Class IV leakage grows with Kv and with the square root of the drop.
leak ∝ Kv · √ΔP
Try it: close the valve and see what each leakage class allows
A control valve rated for 100 m³/h at 1 bar is fully closed and meets Class IV. How much may it leak?
- Allowed leakage
- 167 mL/min
- Over 24 hours
- 240.0 L
- What you would see
- a steady trickle
- Compared with Class IV
- × 1.00
Class IV: the standard for metal-seated control valves, and a good general choice.
5Units and formulas
Leakage in mL/min (or bubbles per minute for Class VI, tested with air). Classes II to IV use a percentage of the rated flow capacity. Class V is in mL of water per minute per inch of seat diameter per psi of pressure drop.
Formulas
- Class II: 0.5% of rated capacity
- Class III: 0.1%
- Class IV: 0.01%
- Class V: 5 × 10⁻⁴ mL/min per inch of seat diameter per psi
- Class VI: table by seat diameter (4 in: 1.7 mL/min of air)
6Why it matters, and common mistakes
Why it matters
- ✓Leakage past a closed valve can waste product, or be dangerous if the fluid is toxic or flammable.
- ✓It decides whether a control valve can also isolate, or whether you need a separate block valve.
- ✓It is a required line on a control valve datasheet.
Common mistakes
- !Assuming a control valve gives bubble-tight shut-off by default.
- !Specifying Class VI for a metal-seated valve that cannot reach it.
- !Forgetting that leakage rises as the seat wears.
Keep going: more on valves and systems
Flow characteristics
How flow changes as a valve opens: linear, equal percentage and quick opening.
Open lesson →
Valve authority and rangeability
How much of the system pressure drop the valve controls, and how far it can turn down.
Open lesson →
Flashing and choked flow
When the flow stops rising however much the pressure drop grows.
Open lesson →
Minor losses (K factor)
What valves, bends and reducers cost in pressure.
Open lesson →
Pump and system curves
Where a pump and a pipe system balance: the operating point.
Open lesson →
NPSH
Whether a pump has enough pressure at its inlet to avoid cavitation.
Open lesson →
Gas and steam flow
Compressible flow through a valve: expansion and the sonic limit.
Open lesson →
Control loop basics
Setpoint, gain, deadband and PID in plain words.
Open lesson →
Signals and fail-safe positions
4–20 mA, pneumatic signals, and what a valve does when power fails.
Open lesson →
Noise and vibration
Why valves are loud, how sound adds up and fades, and what to do about it.
Open lesson →
Materials and corrosion
Choosing a valve body material that survives the fluid and the temperature.
Open lesson →